| PROGRAMMABLE ONOFF CONTROLLER ----------------------------------------------------------LC96S |
| |
| LOW COST, 1-ROW DISPLAY---------------------------------------------------------------VER 11.XX |
| |

|
- Inputs : J, K, Pt100
- 0/ 1 setpoint
- 85~265 V AC SMPS
- Control : ONOFF and Time Proportional
- Accuracy : ±0.1% of full scale ± 1° C, typical
- Sensor break indication
|
| |
| Specification |
| |
| Input |
|
| Inut types |
|
| Thermocouple |
J, K |
| RTD |
Pt100 |
| Range limits |
See Table 1 |
| Accuracy |
See Table 1 |
| Cold junction |
Automatic |
| compensation |
|
| Temperature coefficient |
|
| of accuracy |
±0.5% of span / 25 °C |
| Units |
°C (For °F, contat us) |
| Outputs |
|
| No. of relays |
0 / 1 electromagnetic relay |
| Relay contact type |
NO-C-NC |
| Relay contact rating |
5A / 230V AC, resistive |
| SSR drive |
12V DC drive signal for external SSR |
| Mutual isolation between |
1KV AC / 1 minute |
| input / output / supply |
|
| Indication |
|
| Display |
4 digit, 7 segment 0.56" (14.2 mm) red LED display |
| Status indication |
LED for relay status |
| Programmable Parameters |
|
|
| Input |
|
| Setpoint |
Full range (See Table 1) |
| Hysteresis / band |
0.1 to 99.9 |
| Resolution |
0.1, 1 |
| Bias |
-99.9 to 99.9 |
| High scale |
Full range (See Table 1) |
| Low scale |
Full range (See Table 1) |
| Control functions |
ONOFF, Time Proportional Control (TPC) |
| Cycle time for TPC |
1~99 seconds |
| Relay logic |
a. Heat b. Cool |
| Proportional offset |
-99.9 to 99.9 |
| Other |
|
| Keyboard |
Tactile, 3 keys |
| Enclosure construction |
Plug-in (circuit removable without affecting terminal wiring) |
| Dimensions (in mm) |
96(H) x 96(W) x 100(D) |
| Mounting |
Panel mount |
| Panel cutout |
92 x 92 mm |
| Supply voltage |
85~265 V AC, 50 Hz |
| Power consumption |
3 watts maximum |
| Operating ambient |
0 ~50°C |
| temperature |
|
| Relative humidity |
Below 90%, non condensing |
|
|
| |
| Relay Logic |
| |
 |
ONOFF CONTROL |
TIME PROPORTIONAL CONTROL |
|
| |
| |
| Table1 |
| |
| Sensor / Input |
Range Limits |
Range In Which |
Typical Accuracy |
Worst Case |
| (°C / EU ) |
Accuracy Is Specified |
At 30 °C |
Accuracy At 30 °C |
| Low Scale |
High Scale |
Low Scale |
High Scale |
(°C / EU ) |
(°C / EU ) |
| Iron / Constantan (J) |
-99 |
760 |
0 |
760 |
±1 |
±3 |
| Chromel / Alumel (K) |
-99 |
1372 |
-50 |
1200 |
±1 |
±3 |
| Pt100, 3-wire |
-99 |
850 |
-50 |
850 |
±0.5* |
±2.o |
| * ± 0.1 °C in the range -50 to + 400 °C |
|
| |
| |
| Connection Diagram |
| |
 |
| |
|
|