| PROGRAMMABLE ONOFF CONTROLLER -----------------------------------------------------------------------------MC96 |
| |
| |

|
- Different combinatins of 3 inputs from 8
thermocouple
types, Pt100, 0/4~20 mA
- 0 / 1 / 2 setpoints
- Isolated 0/4~20 mA or 0~10 V DC
retransmission
output
- 85~265 V AC SMPS
- Functions : ONOFF and Time Proportional
- Accuracy :±o.1% of full scale ± 1°C, typical
- Sensor break indiation
|
| |
| Specification |
| |
| Input |
|
| Input types |
|
| Thermocouple |
B, E, J, K, N, R, S, T |
| RTD |
Pt100 |
| Linear input |
4~20 mA, 0~20 mA |
| Load resistance for |
250Ω, internally provided |
| 0/4~20mA input |
|
| Input type groups |
See ordering information |
| Transmitter supply |
22 V DC, Nominal, 30 mA max |
| Range limits |
See Table 1 |
| Accuracy |
See Table 1 |
| Cold junction |
Automatic |
| Compensation |
|
| Temperature Coefficient |
|
| Of accuracy |
± 0.5% of span / 25 °C |
| Units |
|
| Pt100, Thermocouple |
°C (For °F, contat us) |
| Linear |
EU |
| Outputs |
|
| No. of relays |
0 / 1 / 2 electromagnetic relays |
| Relay contact type |
NO-C-NC |
| Relay contact rating |
5A / 230V AC, resistive |
| SSR drive |
12 V DC drive signal for external SSR |
| Retransmission Output |
Current or voltage |
| Current Output |
4~20 mA / 0~20 mA isolated from input |
| Maximum load for |
600 ohms |
| Current output |
|
| Voltage output |
0~10 V DC isolated from input |
| Load for Voltage |
> 10 Kohms |
|
| Output |
|
| Mutual isolation between |
1 KV AC / 1 minute |
| input / Output / Supply |
|
| Indication |
|
| Display |
Upper : 4 digit, 7 segment 0.56" (14.2mm)red LED display
Lower :4 digit, 7 segment 0.56" (14.2mm)green LED
display |
| Status indication |
2 LEDs for relay status |
| Programmable Parameters |
|
| Setpoint |
Full range (See Table 1) |
| Hysteresis / band |
0.1 to 99.9 °C |
| Resolution |
o.1, 1 |
| High scale |
Full range (See Table 1) |
| Low scale |
Full range (See Table 1) |
| Control functions |
ONOFF, Time Proportional
Control (TPC)(RLY1)
ONOFF (RLY2) |
| Cycle time for TPC |
1~99 seconds |
| Relay logic |
a. Heat b. Cool
|
| Proportional offset |
-99.9 to 99.9 °C(RLY1) |
| Other |
|
| Keyboard |
Tactile, 3 keys |
| Enclosure construction |
Plug - in (circuit removable without affecting terminal wiring) |
| Dimensions (in mm) |
96 (H) x 96 (W) x 100 (D) |
| Mounting |
Panel mount |
| Panel cutout |
92 x 92 mm |
| Supply voltage |
85 ~ 265 V AC, 50 / 60 Hz |
| Power consumption |
3 watts maximum |
| Operating ambient |
0~50 °C |
| temperature |
|
| Relative humidity |
Below 90%, non condensing |
|
|
| |
| Relay Logic |
| |
 |
ONOFF CONTROL |
TIME PROPORTIONAL CONTROL |
|
| |
| |
| Table1 |
| |
| Sensor / Input |
Range Limits |
Range In Which |
Typical Accuracy |
Worst Case |
| (°C / EU ) |
Accuracy Is Specified |
At 30 °C |
Accuracy At 30 °C |
| Low Scale |
High Scale |
Low Scale |
High Scale |
(°C / EU ) |
(°C / EU ) |
| Iron / Constantan (J) |
-99 |
760 |
0 |
760 |
±1 |
±3 |
| Chromel / Alumel (K) |
-99 |
1372 |
-50 |
1200 |
±1 |
±3 |
| Pt / Pt-13% Rh(R) |
0 |
1760 |
0 |
1760 |
±2 |
±5 |
| Pt / Pt-10% Rh(S) |
0 |
1760 |
0 |
1760 |
±2 |
±5 |
| Copper /Constantan(T) |
-99 |
400 |
-50 |
400 |
±1 |
±3 |
| Nicrosil / Nisil (N) |
-99 |
1300 |
-50 |
1200 |
±1 |
±3 |
| Pt - 6% Rh / Pt-30% Rh (B) |
400 |
1820 |
400 |
1820 |
±3 |
±5 |
| Chromel / Constantan (E) |
-99 |
900 |
0 |
800 |
±1 |
±3 |
| Pt100, 3-wire |
-99 |
850 |
-50 |
850 |
±0.5* |
±2.0 |
| Linear 0~20 mA, 4~20 mA |
-1999 |
9999 |
-1999 |
9999 |
±5EU |
±20 EU |
| * ± 0.1 °C in the range -50 to + 400 °C |
|
| |
| |
| Connection Diagram |
| |
 |
| |
|
|