PROGRAMMABLE ONOFF CONTROLLERS --------------------------------------------------------------MCP961, MCP962 |
|
1 & 2 Setpoints, Pushwheel Switches |
|
|
|
|
- Universal input : 8 thermocouples, Pt100,
0/4~20 mA, 0~10 V DC
- 1 & 2 setpoints
- Isolated 0/4~20 mA or 0~10 V DC
retransmission output.
|
- 85~265 V AC SMPS
- Control : ONOFF and Timw Proportional
- Accuracy : ±0.1% of full sale ±1 °C, typical
- Sensor break indication
|
|
|
|
Specifications All specifications at ambient of 25°C , unless specified otherwise |
|
INPUT |
|
Thermocouple |
B, E, J, K, N, R, S, T |
RTD |
Pt100 |
Linear input |
4~20 mA, 0~20 mA, 0~10 V DC |
Load resistance for |
250Ω, internally provided |
0/4~20mA input |
|
Transmitter supply |
22 V DC, Nominal, 30 mA max |
Range limits |
See Table 1 |
Accuracy |
See Table 1 |
Cold junction |
Automatic |
Compensation |
|
Temperature Coefficient |
|
Of accuracy |
± 0.5% of span / 25 °C |
Units |
|
Pt100, Thermocouple |
°C (For °F, contat us) |
Linear |
EU |
SETPOINTS |
|
No. of setpoints |
MCP961 : 1
MCP962 : 2 |
Setpoint settings |
MCP961 : 1 x 4-digit pushwheel switches
MCP962 : 2 x 4-digit pushwheel switches |
Outputs |
|
No. of relays |
MCP961 : 1
MCP962 : 2
|
Relay contact type |
NO-C-NC |
Relay contact rating |
5A / 230V AC, resistive |
SSR drive |
12 V DC drive signal for external SSR |
Retransmission Output |
Current or voltage |
Current Output |
4~20 mA / 0~20 mA isolated from input |
Maximum load for |
600 ohms |
Current output |
|
Voltage output |
0~10 V DC isolated from input |
|
Load for Voltage |
> 10 Kohms |
Output |
|
Mutual isolation between |
1 KV AC / 1 minute |
input / Output / Supply |
|
INDICATION |
|
Display |
4 digit, 7 segment 0.56" (14.2 mm) red LED display
|
Status indication |
2 LEDs for relay status |
PROGRAMMABLE PARAMETERS |
|
Input |
|
Hysteresis / band |
0.1 to 99.9 |
Bias |
-99.9 to 99.9 |
High scale |
Full range (See Table 1) |
Low scale |
Full range (See Table 1) |
Control functions |
ONOFF, Time Proportional Control (TPC)(Relay1)
ONOFF (Relay2) |
Cycle time for TPC |
1~99 seconds |
Relay logic |
a. Heat
b. Cool
c. Full scale high alarm
d. Full scale low alarm
|
Proportional offset |
-99.9 to 99.9 (Relay1) |
OTHER |
|
Keyboard |
Tactiie, 3 keys |
Enclosure construction |
Plug - in (circuit removable without affecting terminal wiring) |
Dimensions (in mm) |
96 (H) x 96 (W) x 100 (D) |
Mounting |
Panel mount |
Panel cutout |
92 x 92 mm |
Supply voltage |
a)85 ~ 265 V AC, 50 / 60 Hz b)20~35 V DC (factory option)
|
Power consumption |
3 watts maximum |
Operating ambient |
0~50 °C |
temperature |
|
Relative humidity |
Below 90%, non condensing |
|
|
|
Relay Logic |
|
|
ONOFF CONTROL (Relay1, Relay2) |
TIME PROPORTIONAL CONTROL (Relay1 only) |
|
|
|
Table1 |
|
Sensor / Input |
Range Limits |
Range In Which |
Typical Accuracy |
Worst Case |
(°C / EU ) |
Accuracy Is Specified |
At 30 °C |
Accuracy At 30 °C |
Low Scale |
High Scale |
Low Scale |
High Scale |
(°C / EU ) |
(°C / EU ) |
Iron / Constantan (J) |
0 |
760 |
0 |
760 |
±1 |
±3 |
Chromel / Alumel (K) |
0 |
1372 |
0 |
1200 |
±1 |
±3 |
Pt / Pt-13% Rh(R) |
0 |
1760 |
0 |
1760 |
±2 |
±5 |
Pt / Pt-10% Rh(S) |
0 |
1760 |
0 |
1760 |
±2 |
±5 |
Copper /Constantan(T) |
0 |
400 |
0 |
400 |
±1 |
±3 |
Nicrosil / Nisil (N) |
0 |
1300 |
0 |
1200 |
±1 |
±3 |
Pt - 6% Rh / Pt-30% Rh (B) |
400 |
1820 |
400 |
1820 |
±3 |
±5 |
Chromel / Constantan (E) |
0 |
900 |
0 |
800 |
±1 |
±3 |
Pt100, 3-wire |
0 |
850 |
0 |
850 |
±0.5 |
±2.0 |
inear 0~20 mA, 4~20 mA, 0~10 V DC |
0 |
9999 |
0 |
9999 |
±5EU |
±20 EU |
|
|
|
Connection Diagram |
|
|
|
|
|