Logo - Madhu Group  
products company profile email contact      
 
 
   
1 2 3 4 5 6 7
   
   
  Products >>> Universal Signal Conditional Module configuration / operating the function keys
     
   
 
configuration / operating the function keys  

Signal and sensor error info via display front HHT 4624

Sensor error (see limits in the table) is displayed as SE.BR (sensor break). Signals outside the selected range (not sensor error, see table for limits) are displayed as IN.LO indicating low input signal or IN.HI indicating high input signal. The error indication is displayed in line 1 as text.

Signal and sensor error indication without display front

Status of the unit can also be read from the green LED in the front of the device.
Green flashing LED 13 Hz indicates normal operation.
Green flashing LED 1 Hz indicates sensor error.

Relay functions

5 different settings of relay function can be selected.

Setpoint: The unit works as a single limit switch

Window: The relay has a window that is defined by a low and a high setpoint. On both sides of the window the relay has the same status.

Error function: The relay is activated by sensor error.

Power: The relay is activated as long as the power is on.

Off: The relay is deactivated.

Increasing/decreasing: The relays can be set to activate at increasing or
decreasing input signal.

Delay: An ON and an OFF delay can be set on both relays in the range 0...3600 s.

Hysteresis: A hysteresis can be set at 0.1...25% of the span. The window function is selected by choosing ”window” in the menu and defining a high and a low setpoint.

It can be selected for each relay contact whether the contact is open or closed inside the window. This selection is made in the menu R1.cont and R2.cont.

The setpoint function is selected by choosing ”setpoint” in the menu and entering the desired limit. The device then works as a single limit switch.

An activated relay means that the contact is closed if the contact function ”normally open” is selected, and the contact is open if the contact function”normally closed” is selected.

The delay time for activation and deactivation can be set independently of each other in the menus ON.DEL and OFF DEL respectively.

Advanced functions

The device gives access to a number of advanced functions which can be reached by answering “Yes” to the point “adv.set”.

Two-point process calibration: The device can be process-calibrated in 2 points to fit a given input signal . A low input signal (not necessarily 0%) is applied and the actual value is entered. Then a high signal (not necessarily 100%) is applied and the actual value is entered. If you accept to use the calibration, the device will work according to this new adjustment.

 
INPUT Values to be entered in
current uA
Voltage mV
Lin.R ohms
POT %
RTD milli ohms
TC uV

Process simulation function: If you agree to the point “EN.SIM” it is possible to simulate an input signal by means of the arrow keys and thus control the output signal up or down. Pressing and holding the OK will return to the default state 1.0

Password: Here you can choose a password between 0000 and 9999 in order to protect the device against unauthorised modifications to the configuration. The device is delivered default without password.

Selection of units

After choosing the input signal type you can choose which process units should be displayed in text line 1 (see table). By selection of temperature input the process value is always displayed in Celsius or Fahrenheit. This is selected in the menu point after selection of temperature input.

 
     
1 2 3 4 5 6 7
 

Copyright and Privacy Statement Madhu Group