INPUT |
|
Inut |
Basic RH and T signals from sensor |
Compatible sensors |
RSHT20
(General purpose / wall mount)
RSHT30(Wall Mount)
RSHT40(Duct mount)
RSHT20, RSHT30 & RSHT40 must be ordered separately |
Distance between sensor & instrument |
|
Range |
0~100% RH
-20~100 °C(32~212 °F)
Also see sensor range and Fig 1 |
Resolution |
0.1 or 1 |
Accuracy |
± 3% RH, ± 0.3 °C |
Outputs |
|
No of relays |
0/1/2 electromagnetic relays |
Relay contact type |
NO-C-NC |
Relay contact rating |
5A / 230V AC, resistive |
SSR drive |
12 V DC drive signal for
external SSR |
Retransmission output |
Current or voltage corresponding or RH or T |
Current output |
4~20 mA / 0~20 mA isolated from input |
Maximum load for |
600 ohms |
current output |
|
Voltage output |
0~10 V DC isolated from input |
Load for voltage |
>10 Kohms |
ouput |
|
Mutual isolation between |
1KV AC / 1 minute |
input / output / supply |
|
Indication |
|
|
Display |
Upper : 4 digit, 7 segment
0.56" (14.2mm) green LED
display LOWER : 4 digit, 7
segment 0.56" (14.2 mm)
red LED display |
Status Indication |
2 LEDs for relay status |
PROGRAMMABLE
PATAMETERS |
|
Unit |
°C, °F |
Resolution |
User selectable
0.1, 1 |
Relays |
0 / 1 / 2 corresponding to RH and / or T |
Setpoint |
0~100 |
Hysterisis |
0.1~99.9 |
Bias for RH & T |
-10 to 10 |
Relay logic |
a. Full Scale Hi
b. Full Scale Lo
|
Retransmission output |
Corresponding to RH or T |
High scale(output) |
0~100 |
Low scale (output) |
0~100 |
other |
|
Keyboard |
Tactile, 3 keys |
Enclosure construction |
Plug-in (circuit removable
without affecting terminal wiring) |
Dimensions(in mm) |
96(W) x 96(H) x 100(D) |
Mounting |
Panel mount |
Panel cutout |
92 x 92 mm |
Supply voltage |
a)85~265 V AC, 50/60 Hz
b)20~35 V DC (optional) |
Power consumption |
3 watts maximum |
Operating ambient |
0~50°C |
temperature |
|
Relative humidity |