Logo - Madhu Group  
products company profile email contact      
 
 
   
1 2 3 4 5 6
  Products  >>> Universal Signal Conditional Module / Universal Transmitter
     
   
 
 
Output Range readout (IN.LO , IN.HI)
If the valid range of the A/D converter or the polynomial is exceeded
Input Range Read Out Limit
VOLT For All Ranges IN.LO <0V
IN.HI >10V
CURR 0..20mA / 4..20mA IN.LO <-1.05mA
IN.HI >25.05mA
LIN.R 0..10KΩ IN.LO <0Ω
IN.HI <10kΩ
POTM - IN.LO <-0.5%
IN.HI >100.05%
TEMP TC / RTD IN.LO <Temp range
IN.HI >Temp range
Display readout below min.- / above max. (-1999, 9999)
Input Range Read Out Limit
All All -1999 Disp readout <-1999
9999 Disp readout >9999
Sensor error detection limits
Sensor error detection (SE.BR):
Input Range Read Out Limit
CURR Loop break (4..20 mA) SE.BR <= 3.6 mA; > = 21 mA
POTM All, SE.BR on all 3-wire SE.BR > 110%
LIN.R 0..10KΩ SE.BR > 10.2KΩ
TEMP TC SE.BR > 78mV
RTD, 2-, 3-, and 4-wire SE.BR > 4KΩ
Error Indications
Readout at hardware error
Error search Read Out Error Cause
Test of internal CJC sensor CJ.ER CJC sensor defect or temperat ure outside range (-20°C-60°C)
Checksum test of the configuration in FLASH Checksum
.ER
Error in FLASH
Test Of Communication Link Comm.tout Link Between transmitter and HHT Fails
 
     
1 2 3 4 5 6
 

Copyright and Privacy Statement Madhu Group